You are here · Zone E · Alarm panel

The fire alarm control panel: what the F-80 holder reads and presses

The fire alarm control panel (FACP) is where the holder of the F-80 Certificate of Fitness reads what the alarm system reports and takes the first actions. It shows three kinds of signal: alarm, supervisory and trouble (Source: Study Material §10.1). The coordinator must know each control on the panel, check that its lights work, and know where its backup power comes from.

Plan ref E3 concept roomsUpdated October 25, 2026

Alarm, supervisory, trouble

The three FACP signals, Study Material sections 10.1 and 10.8

SignalAlarmSupervisoryTrouble
What it means (differs)A device that shows fire has activated.A monitored system or device is compromised or off-normal.A fault in a monitored circuit or component.
Typical causes (differs)A manual pull station, an automatic detector, a water flow switch.A closed sprinkler control valve, a tank too low or too cold, a fire pump fault.A low battery, an AC power failure, a phone line failure.
Your first move (differs)Report to the panel and carry out the plan. An unplanned, unannounced alarm is a real fire.Find the supervised device behind it; some panels show only a general signal. Get it resolved immediately.Find out what failed. An authorized technician repairs or replaces defective equipment at once.

Shaded rows marked ≠ are the points where at least one column differs from the others.

Anything impaired goes to the impairment coordinator immediately (Source: Study Material §10). Each signal’s full response, row by row, is on alarm, supervisory or trouble.

Reset comes last

An option that resets the panel to see whether the alarm comes back fails twice. The Study Material says never reset until FDNY personnel verify the condition, and a device still in alarm only starts a new alarm (Source: Study Material §10.1).

Reading the panel, reading the options

Scan the options first. If two of them name signals, the stem only has to tell you one thing: does it show fire, an off-normal device, or a failure? A closed valve and a dead battery both need fixing, but they are different signals, and options can be built around exactly that mix-up.

Acknowledge, alarm silence and reset all make the panel quieter in some way, and each has its own condition. Acknowledge, silence, reset works through them one by one.

The panel tasks you must be able to show are part of the coordinator role. What feeds signals into the panel, from detectors to pull stations, is on the alarm devices page. The panel tells you; it does not let you change the system. Installing or modifying components is off limits to the coordinator (Source: Study Material §10).

Checkpoints for Zone E: Alarm panel

Checkpoint round

0 of 13 checked · 0 cleared

Practice questions written for study, not taken from the test. The real F-80 is a multiple-choice test on a touch-screen computer at FDNY Headquarters.

Panel checkpoints reward patience. Read all four options, then strike any that resets, silences or changes something before the rule allows it.

How the checkpoint round works

Read the options first and rule out the ones that break a rule, then pick from what is left. After you answer, the debrief explains every option and scores your strikes. Keys: 1–5 or A–E answer, Shift with a number rules that option out, the arrow keys move.

Checkpoint 1 of 13

  1. Checkpoint 01

    An ALARM signal activates on the primary FACP at a shelter. Which sequence of immediate actions MUST the coordinator follow?

    Rule out what you can with the ✕ buttons, then choose. The debrief for every option opens here.

    1. ACorrect: Any unplanned alarm is treated as a real fire, so the coordinator reads the panel, runs the plan and makes sure the FDNY is told.
    2. BWaiting for a radio report before notifying anyone delays the response to what must be treated as a real fire.
    3. CSilencing needs FDNY authorization, and waiting passively skips the plan.
    4. DSilencing locally needs FDNY authorization, and a vendor is not the first call during an alarm.
  2. Checkpoint 02

    The fire alarm control panel sounds a steady chime and shows a trouble signal for a faulty circuit. What is the MOST appropriate immediate action?

    Rule out what you can with the ✕ buttons, then choose. The debrief for every option opens here.

    1. AOff-line status is only for drills and other purposes the FDNY allows, and never without telling anyone.
    2. BLeaving the chime on adds nothing once the signal is known; acknowledge it and act on it.
    3. CA reset does not clear trouble conditions; most clear on their own once the fault is fixed.
    4. DCorrect: ACK silences the panel, but a trouble signal still has to be investigated, corrected and recorded.
  3. Checkpoint 03

    The primary FACP indicates an AC power loss during a localized grid failure. The panel is currently operating on secondary power. Which multi-step response is MOST appropriate for the coordinator?

    Rule out what you can with the ✕ buttons, then choose. The debrief for every option opens here.

    1. ASilencing and waiting ignores that the batteries will run down; the panel needs follow-up now.
    2. BA reset cannot bring back utility power, and it does not clear trouble conditions.
    3. CCorrect: Secondary power should take over within 10 seconds, but it is limited, so confirm it, report it and plan for an impairment.
    4. DThe system still works on secondary power, so a full evacuation is not the first step.
  4. Checkpoint 04

    During an extended power outage, the fire alarm system has been operating on backup batteries. The panel now indicates the battery capacity is critically low. Which action must be taken?

    Rule out what you can with the ✕ buttons, then choose. The debrief for every option opens here.

    1. AA dying battery means the system is about to stop working; silencing the signal ignores that.
    2. BCorrect: A system that cannot stay powered is going out of service, which means notifying the FDNY and setting up a fire watch.
    3. CWaiting for the utility leaves the shelter without a working alarm system and no backup plan.
    4. DShutting the panel down removes protection entirely, the opposite of what is needed.
  5. Checkpoint 05

    A staff member suggests changing the panel settings to deal with a smoke detector that keeps acting up. Which of these is the coordinator never allowed to do?

    Rule out what you can with the ✕ buttons, then choose. The debrief for every option opens here.

    1. ASending trained staff to check an alarm zone is a normal part of responding to a signal.
    2. BAlternate protections during an impairment are required, not forbidden.
    3. CAcknowledging signals at the panel is one of the coordinator’s listed panel tasks.
    4. DCorrect: Coordinators are prohibited from installing or modifying fire alarm components; device and panel changes belong to authorized technicians.
  6. Checkpoint 06

    The FACP is running on battery during a long power outage. A maintenance worker suggests turning off some detector zones to save battery. What is the MOST appropriate response?

    Rule out what you can with the ✕ buttons, then choose. The debrief for every option opens here.

    1. ATelling the central station does not make switching off detection acceptable; those zones would still be unprotected.
    2. BTurning off detector zones leaves parts of the shelter unprotected, and coordinators may not alter the system.
    3. CLogging it later does not change that disabling zones is not the coordinator’s call.
    4. DCorrect: Coordinators may not modify the fire alarm system; a low battery is handled through impairment steps, not by cutting zones.
  7. Checkpoint 07

    During a check of the panel, the coordinator finds that a third-floor smoke detection zone was turned off without permission. What is the MOST appropriate action?

    Rule out what you can with the ✕ buttons, then choose. The debrief for every option opens here.

    1. ACorrect: A disabled zone is an out-of-service condition, so the owner is told and the impairment steps run until it is restored.
    2. BAsking around first leaves the floor unprotected while you wait for answers.
    3. CWaiting for the next visit can leave the floor without detection for weeks.
    4. DA reset is for clearing a verified alarm, not for changing the system, and it does not re-enable a disabled zone.
  8. Checkpoint 08

    What does the lamp test on the fire alarm control panel check, and how often should the coordinator do it?

    Rule out what you can with the ✕ buttons, then choose. The debrief for every option opens here.

    1. AOut: the lamp test checks the panel’s own lights, not the strobes out on the floors.
    2. BCorrect: it checks that every LED on the panel works, and the coordinator does it daily.
    3. CBatteries are a secondary power source; the lamp test does not check them.
    4. DRight device, wrong interval: the Study Material says the lamp test is daily.
  9. Checkpoint 09

    If primary power to a shelter’s fire alarm system fails, the secondary power supply must take over within how long?

    Rule out what you can with the ✕ buttons, then choose. The debrief for every option opens here.

    1. ACorrect: batteries or a generator must power the system within 10 seconds of a primary power failure.
    2. BToo slow: the Study Material limit is 10 seconds.
    3. COut: a full minute without power is far beyond the 10-second limit.
    4. DMinutes are much too long; the takeover limit is counted in seconds, at 10.
  10. Checkpoint 10

    When a remote annunciator panel is installed in a shelter, what is its function?

    Rule out what you can with the ✕ buttons, then choose. The debrief for every option opens here.

    1. AOut: the annunciator has no reset role; resetting is done at the fire alarm control panel.
    2. BSignals go to the central station from the FACP and its transmitter, not from the annunciator.
    3. CHorns and strobes are notification devices driven by the FACP, not by the annunciator.
    4. DCorrect: its only job is a visual display of alarm, supervisory or trouble conditions.
  11. Checkpoint 11

    What does the Study Material say about clearing a trouble condition on the fire alarm control panel?

    Rule out what you can with the ✕ buttons, then choose. The debrief for every option opens here.

    1. AOut: a reset does not clear trouble conditions at all.
    2. BThis is reversed: a reset is often needed for supervisory conditions, while trouble does not clear with a reset.
    3. CCorrect: trouble usually clears on its own once the fault is gone; until then, investigate and correct it.
    4. DAcknowledge only acknowledges the signal and silences the panel; it does not reset anything.
  12. Checkpoint 12

    Which of these does the Study Material accept as a secondary power supply for a shelter’s fire alarm system?

    Rule out what you can with the ✕ buttons, then choose. The debrief for every option opens here.

    1. AA shared building circuit can fail with the rest of the power; the backup has to serve the alarm system.
    2. BA battery shared with other equipment is not dedicated to the alarm system and may be drained when it is needed.
    3. CCorrect: Storage batteries dedicated to the fire alarm system are an accepted secondary source, and so are engine-driven generators.
    4. DA generator brought in after a failure cannot power the system within 10 seconds; the Study Material accepts dedicated storage batteries or engine-driven generators.
  13. Checkpoint 13

    A smoke detector sends an alarm signal to the fire alarm control panel. Besides sounding the horns and strobes, what does the panel do?

    Rule out what you can with the ✕ buttons, then choose. The debrief for every option opens here.

    1. AThe panel does not wait for staff; the signal goes out right away, and staff treat the alarm as a real fire.
    2. BAn alarm signal does leave the building: the central station receives it and reports it to the FDNY.
    3. CBattery power takes over when primary power fails, not because a detector senses smoke.
    4. DCorrect: On an alarm signal the panel sounds the horns and strobes, sends a signal to a central station company, and triggers certain building functions.

The panel controls

FACP controls in the Study Material, section 10.1

ControlWhat it doesThe condition
Acknowledge (ACK)Acknowledges alarm, trouble or supervisory signals and silences the panel itself.One of the panel tasks the coordinator must be able to show.
Alarm silenceSilences the building’s audible devices, and on some systems the strobes too, after evacuation is complete. The central station still gets the signal.Only with FDNY authorization.
ResetReturns the system to normal after the alarm condition is cleared. A device still in alarm starts a new alarm.Never before FDNY personnel verify the condition.
Lamp testLights every LED on the panel to prove they all work.Daily, by the coordinator.
Fan restartRestarts air handling fans that the alarm shut down. A reset alone usually does not.Usually a separate key, switch or button at the FACP.

The fan restart is in Source: Study Material §13.1.

Where the signals go, and the power behind them

Every signal, alarm, supervisory and trouble alike, goes to the FDNY-approved central station (Source: Study Material §10.8). On an alarm, the panel also sounds the horns and strobes and triggers building functions (Source: Study Material §10.1).

The primary power supply is a dedicated circuit from the local utility. The secondary supply must power the system within 10 seconds of a primary failure. Storage batteries dedicated to the fire alarm system, or engine-driven generators, are acceptable secondary sources (Source: Study Material §10.2).

Where the rule is written