F-80 flashcards: the numbers and rules people mix up

Twenty-eight cards for the numbers and paired terms that are easiest to swap. Each back names its section of the FDNY Study Material, revised January 2026. Definitions in full are in the key terms zone; for rules in action, run the mixed practice round.

Plan ref 9Updated October 25, 2026

The deck, in look-alike pairs

Say the back out loud before you open a card. Cards that sit next to each other are the ones the options mix up.

  • 01Alarm signal

    A signal from a device whose activation means fire: a pull station, a detector or a water-flow switch. Study Material §10.1.

  • 02Supervisory signal

    A monitored system or device is compromised or not normal, for example a closed sprinkler valve. Study Material §10.1, §10.8.

  • 03Trouble signal

    A fault in a monitored circuit or part, for example a low battery or a lost phone line. Study Material §10.1.

  • 04Acknowledge

    Tells the panel you saw the signal and quiets the panel itself. The building horns keep sounding. Study Material §10.1.

  • 05Alarm silence

    Silences the building horns (on some systems the strobes too) once evacuation is complete, and only with FDNY authorization. The central station still gets the signal. Study Material §4, §10.1.

  • 06Reset

    Only after the condition is cleared and verified by FDNY personnel. Study Material §10.1.

  • 07Smoke alarm

    Sensor, sounder and power in one unit, not connected to a system. Study Material §2.

  • 08Smoke detector

    Senses smoke and is connected to the fire alarm control panel. Study Material §2.

  • 09Unnecessary alarm

    The system worked as designed, but no FDNY response was needed. Example: cigarette smoke in a non-smoking area. Study Material §2.

  • 10Unwarranted alarm

    The system failed to work as designed: poor detector placement, a wrong setting, poor maintenance or a malfunction. Study Material §2.

  • 11Off-line

    A period when the central station, at the owner’s request, does not send alarm signals to the FDNY. Allowed only for Fire Department purposes such as a drill. Study Material §2.

  • 12Lamp test

    Checks that every light on the panel works. The coordinator runs it daily. Study Material §10.1.

  • 13Secondary power

    Takes over within 10 seconds of a primary power failure. Study Material §10.2.

  • 14Rate-of-rise heat detector

    Activates when the temperature climbs 12° to 15°F per minute. Study Material §10.3.

  • 15Smoke detector cleaning

    Every 6 months, by an S-97 or S-98 holder. The F-80 holder does not service detectors. Study Material §10.3.

  • 16Pull station placement

    Handle about 4 ft above the floor, within 5 ft of the exit door (stations installed or moved after April 1, 1984). Study Material §10.4.

  • 17Selective alarm

    Sounds on the fire floor, the floor above and the floor below. A general alarm sounds everywhere. Study Material §10.10.

  • 18Shelter fire guard patrol

    Every area of the building at least once an hour. Study Material §4.1.

  • 19Fire drills in a shelter

    Monthly, on each shift, for all occupants. Study Material §7.3.

  • 20FEP staff refresher training

    At least 1 hour, quarterly, on each work shift. Study Material §6.

  • 21Log book retention

    Kept on the premises for 3 years from the last entry. Study Material §16.

  • 22Fire watch, first 4 hours

    For an area up to 50,000 sq ft, the impairment coordinator or a trained person may keep the watch. Study Material §14.3.

  • 23Fire watch after 4 hours

    Certificate of Fitness fire guards, one per 50,000 sq ft, until the system is restored. Study Material §14.3.

  • 24Minor defect left open

    Not corrected within 30 days: report it to the FDNY in writing. Study Material §14.2.

  • 25Extinguisher up to 40 lb

    Top no higher than 5 ft; bottom at least 4 in off the floor. Study Material §15.

  • 26Extinguisher over 40 lb

    Top no higher than 3.5 ft; bottom still at least 4 in off the floor. Study Material §15.

  • 27Extinguisher checks

    A monthly quick check, noted on the tag, and an annual service by a W-96 holder. Study Material §15.3.

  • 28PASS

    Pull, Aim, Squeeze, Sweep. Study Material §15.

Why the cards come in pairs

A wrong option in a practice round is often the twin of the right one. A trouble signal sits where a supervisory signal belongs. An extinguisher over 40 lb gets the 5 ft height. The first four hours of a fire watch get the rule for the hours after.

So learn each card together with its twin. When an option looks right, ask which twin it is. Then check the one detail that tells them apart: connected or not, worked as designed or not, before 4 hours or after.

Note

Every number here is the Study Material figure. Where the Fire Code gives a different figure for other buildings, the card keeps the Study Material one, because this site teaches the Study Material figure.

Tip

Ten cards a day fit into a break. The F-80 study plan sets the deck into the last days before the test.